3
Critical
8
High
14
Medium
5
Acknowledged
23
Resolved Hari Ini
Daftar Alert Aktif & Terkini
Menampilkan 10 dari 30 alert · Diperbarui 10 Mar 2026, 14:22 WIB
Critical
Inverter Offline > 30 Menit
Tidak ada data dari inverter selama 47 menit. WireGuard tunnel aktif tapi Modbus timeout pada register 40001.
Critical
PLN Total Outage
PLN import = 0 kWh selama lebih dari 2 jam. PLTS auto-shutdown aktif (anti-islanding protection).
Critical
Inverter Fault Code F003
SunSpec fault register 40107: Grid Overvoltage. V_AC = 247V melebihi threshold 245V. Inverter trip otomatis.
High
Low Performance Ratio — PR 54.2%
Actual PR 54.2% vs expected 73.1% (selisih 18.9%). Kemungkinan panel kotor atau shading parsial. Perlu inspeksi lapangan segera.
High
Communication Error ×5 Berturut-turut
5 kali Modbus TCP timeout berturut-turut. Gateway IoT merespons ping tapi port 502 tidak dapat diakses.
High
Suhu Inverter Tinggi — 68°C
Temperatur heatsink inverter 68°C melebihi threshold 65°C. Cek ventilasi ruang inverter dan filter kipas pendingin.
Medium
Data Gap 15 Menit — 15:45–16:00 WIB
Tidak ada data telemetri selama 15 menit (15:45–16:00 WIB). Kemungkinan gangguan jaringan lokal sementara.
Medium
PR Menurun 2 Bulan Berturut-turut
Trend analytics mendeteksi penurunan PR selama 2 bulan berturut-turut: Jan 70.2% → Feb 66.8% → Mar 63.1% (proyeksi).
✅ Resolved
Inverter Reconnected — Auto Resolved
Downtime 12 menit, auto-resolved setelah koneksi Modbus kembali normal. Total produksi hilang estimasi 0.8 kWh.
✅ Auto-Resolved · Downtime 12 mnt
✅ Resolved
PLN Supply Restored
PLN supply kembali normal pukul 12:30 WIB. PLTS restart otomatis setelah anti-islanding protection 5 menit.
✅ Resolved oleh Teknisi · 12:30 WIB
⚙ Konfigurasi Alert Rules
7 rules aktif · Terakhir diperbarui 01 Mar 2026
| Rule | Kondisi | Threshold | Severity | Cooldown |
|---|---|---|---|---|
| inverter_offline | Tidak ada data | > 30 mnt | Critical | 60 mnt |
| pln_outage | E_import = 0 | > 15 mnt | Critical | 120 mnt |
| low_pr | PR < threshold | 65% | High | 60 mnt |
| high_temperature | Temp inverter | > 65°C | High | 30 mnt |
| comm_error | Modbus timeout | 5× berturut | High | 60 mnt |
| data_gap | Tidak ada data | > 15 mnt | Medium | 30 mnt |
| pr_declining | Trend turun | 2 bulan | Medium | 7 hari |
📡 Notification Channels
3 saluran aktif
@kai_ems_alerts
Telegram Bot · Semua alert
✅ Aktif
energy-manager@kai.id
Email · Critical & High
✅ Aktif
daop-manager@kai.id
Email · DAOP alerts only
✅ Aktif
⚠ Anti-flood: maks. 3 pesan / 10 menit per alert rule aktif
📈 Volume Alert — 30 Hari Terakhir
Stacked: Critical · High · Medium · Tren menurun ✓
🥧 Distribusi Kategori Alert
Berdasarkan 30 hari terakhir (847 alert total)