INV-GMB-001
NORMAL OPERATION
Huawei SUN2000-25KTL-M3
Modbus TCP 192.168.10.51:502 Slave ID: 1 SN: 21223KTL3A012847
Fasilitas
Stasiun Gambir
DAOP 1 Jakarta
Last data:
14:23:07 WIB
P_AC Output
19.2 kW
25 kWp rated
P_DC Input
19.94 kW
487.3V × 39.4A
🔋
Efisiensi DC→AC
96.3 %
Target ≥ 95%
✓ GOOD
📈
Performance Ratio
77.1 %
Target ≥ 75%
🎯
E_day
93.8 kWh
Total: 42,847 kWh
Hari ini
☀️
Temperature
42 °C
Batas: 65°C
NORMAL
🌡️
Register Modbus — Real-time
Modbus TCP · 192.168.10.51:502 · Slave ID: 1
Poll interval: 5s
Register Parameter Raw Value Unit Scale Nilai Aktual Status
32080 Active Power (P_AC) 19200 W ×1 19.200 kW
32078 Reactive Power (Q) 1840 var ×1 1.840 kvar
32064 Phase A Voltage (V_L1) 2203 V ×0.1 220.3 V
32066 Phase B Voltage (V_L2) 2198 V ×0.1 219.8 V
32068 Phase C Voltage (V_L3) 2211 V ×0.1 221.1 V
32069 Phase A Current (I_L1) 292 A ×0.01 29.2 A
32085 Grid Frequency 4997 Hz ×0.01 49.97 Hz
32016 DC Voltage String 1 (V_DC) 4873 V ×0.1 487.3 V
32018 DC Current String 1 (I_DC) 394 A ×0.01 39.4 A
32114 Daily Energy (E_day) 938 kWh ×0.1 93.8 kWh
32106 Total Energy (E_total) 42847 kWh ×1 42,847 kWh
32087 Cabinet Temperature 420 °C ×0.1 42.0 °C
32089 Insulation Resistance 1840 ×1 1,840 kΩ
32008 Device Status Code 512 0x0200 NORMAL
32017 DC Voltage String 2 4858 V ×0.1 485.8 V
32019 DC Current String 2 389 A ×0.01 38.9 A
Power Flow Diagram
☀️ SOLAR PANELS 487.3V 39.4A DC Bus 19.94 kW 🔄 INVERTER SUN2000 η=96.3% eff: 96.3% 19.2 kW AC Out 🔌 GRID PLN 220V AC 50 Hz PF 0.98 2 Strings MPP: 487V 25 kWp Konversi Loss: 0.74 kW (3.7%)
String Monitor
String V_DC I_DC P_DC Status
String 1 487.3 V 39.4 A 19.21 kW NORMAL
String 2 485.8 V 38.9 A 18.90 kW ΔV ±8.3V
⚠ String voltage imbalance terdeteksi: ΔV = 1.5V (threshold: 5V). Pantau dan jadwalkan inspeksi.
Kurva Daya Hari Ini
P_AC vs Kemarin · INV-GMB-001
Hari ini Kemarin
Tren Efisiensi & PR — 30 Hari
Daily efficiency (%) dan Performance Ratio (%)
Efisiensi PR
Riwayat Fault — INV-GMB-001
Total fault: 8 · Active: 1 · Resolved: 7
Menampilkan 12 bulan terakhir
Fault Code Deskripsi Severity Waktu Mulai Waktu Selesai Durasi Status
2025 String voltage imbalance (ΔV > 5V) WARNING 10 Mar 2026 13:47 36+ min ACTIVE
1100 Grid frequency out of range (f < 49.80 Hz) WARNING 09 Mar 2026 11:20 09 Mar 2026 11:23 3 min RESOLVED
3108 Temperature over limit (T > 45°C) WARNING 05 Mar 2026 13:05 05 Mar 2026 14:41 96 min RESOLVED
6120 Communication loss (Modbus timeout) FAULT 02 Mar 2026 16:49 02 Mar 2026 16:51 2 min RESOLVED
2010 Insulation resistance low (R < 1000 kΩ) FAULT 18 Feb 2026 08:15 18 Feb 2026 10:30 2h 15m RESOLVED
1100 Grid voltage out of range (V_L1 > 242V) WARNING 05 Feb 2026 14:32 05 Feb 2026 14:38 6 min RESOLVED
String Monitor — Detail
String Detail — Real-time
String V_DC (V) I_DC (A) P_DC (kW) ΔV vs Avg Status
String 1 487.3 39.4 19.21 +4.2V NORMAL
String 2 485.8 38.9 18.90 -2.8V WATCH
Rata-rata V_DC: 486.55V  ·  Total P_DC: 38.11 kW  ·  ΔV antar string: 1.5V
Distribusi Daya per String
Konfigurasi Inverter
Informasi Perangkat
Model SUN2000-25KTL-M3
Serial Number 21223KTL3A012847
Firmware Version V200R001C00SPC026
Kapasitas AC 25 kW
Kapasitas DC Max 30 kWp
V_DC Range 200V – 1000V
MPPT Range 200V – 950V
Tanggal Instalasi 15 Maret 2024
Konfigurasi Komunikasi
Protokol Modbus TCP/IP
IP Address 192.168.10.51
Port 502
Slave ID 1
Poll Interval 5 detik
Timeout 3 detik
Retry Count
Connection Status CONNECTED